Hempafire XTR 100 is a fire protection coating. Used as intumescent fire protection for structural steel in oil and gas facilities, petrochemical plants and power generation, protecting against hydrocarbon pool fires and jet fires. Hempafire XTR 100 is a two-component epoxy-based intumescent coating providing passive fire protection to structural steel against hydrocarbon pool fires and jet fires. Page parameters: volume solids 100%, number of components: two-component. Comparable products of the same brand: Hempafire 43600, Hempel waterborne marking paint 28100, Hempel pure acrylic marking paint 29680.
Parameter source: HEMPEL manufacturer's Technical Data Sheet (TDS) "Hempafire XTR 100"; values such as spreading rate are converted from TDS parameters and are for product selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.
This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.
| Volume Solids | 100% |
|---|---|
| Dry Film Thickness | — |
| Theoretical Spreading Rate | — |
| VOC | 0 g/L (China) |
| Density / Specific Gravity | Density is 1.0 g/cm³. |
| Number of Components | Two-component |
| Colour / Appearance | Signal grey 17160 |
| Gloss | Semi-gloss |
| Pot Life | 1 h |
For more Q&A on selection, application, acceptance and defect diagnosis, seeFAQsection.
100
Hempafire XTR 100 is a two-component epoxy-based intumescent coating providing passive fire protection to structural steel against hydrocarbon pool fires and jet fires. Tested and certified in accordance with UL 1709 and ISO 22899-1.
Used as intumescent fire protection for structural steel in oil and gas facilities, petrochemical plants and power generation, protecting against hydrocarbon pool fires and jet fires. Suitable for mild steel and galvanized steel.
Certification - design numbers - multiple available covering a range of steelsection types, temperatures and section factors.
- Tested to Chinese fire test standard GB14907 (fire protection coatings for steel structures) and approved.
- Passive fire protection product with fire resistance up to 5 h in the event of a hydrocarbon pool fire - hydrocarbon jet fire protection optimized for shorter durations in downstream projects.
- Hempafire XTR 100 is an efficient solution with shorter DFT and reduced application density.
| Regulations | Value |
| European Union | 19 g/L |
| USA (coatings) | 10 g/L |
| USA (regulatory) | 0 g/L |
| Canada | 0 g/L |
| China | 0 g/L |
| Hong Kong | 0 g/L |
| South Korea | 0 g/L |
Subject to specific legislation; see the explanatory notes on the Hempel website hempel.com or your local Hempel website. This product complies with the VOC requirements of national mandatory or recommended standards; consult the company representative for details.
Handle with care. Before and during use, observe the safety labels on the packaging and paint containers and comply with all local and national safety regulations. Consult the Hempel Safety Data Sheet and Product Data Sheet for the product at all times.
For professional use only.
| Product code | 67820 |
|---|---|
| Product components | Base 67829 |
Hardener 96780
| Standard colour / code | Signal grey 17160 |
|---|
Grey 17160
| Gloss | Semi-gloss |
|---|
100
| Volume solids | 100% |
|---|
Density is 1.0 g/cm³ in accordance with ISO 1183:2004 method A, using multi-component spray application.
- Abrasive blast clean to Sa 2½ (ISO 8501-1) / SP 10 (SSPC) / NACE No.2 minimum.
For further details, refer to the separate Hempel document Surface Preparation Guide.
Base 67829 : Hardener 96780 (2.5 : 1 by weight)
Thinner
| Cleaning solvent | HEMPEL's Thinner 08450 |
|---|
| Product temperature | 25°C | 10°C | 40°C |
| Pot Life | 2 h | 3 h | 1 h |
| Tools | Maximum thinning volume | Application parameters |
| Two-component spray | No thinning required | Not applicable. |
| Trowel | No thinning required | Not applicable. |
(*For other application methods, consult the company representative.)
The dry film thickness of fire protection coatings depends on the required fire resistance period and the section factor of the steel structure; contact the local Hempel representative.
- Theoretical spreading rate: 1 kg of material covers 1 m² at a dry film thickness of 1 mm.
- Practical spreading rate - at an application thickness of 1 mm, 1 kg of Hempafire XTR 100 covers 1 m²
| Surface temperature | 10°C | 25°C | 40°C |
| Hard Dry | 24 h | 11 | 7 |
| Touch Dry | 16 h | 5 | 2 |
100
| Ambient temperature | 25°C |
| Binder | 24 months |
| Curing agent | 24 months |
When stored in unopened original containers, shelf life is counted from the date of production. Thereafter, the product quality must be re-inspected. Storage at high temperatures may shorten the shelf life. The shelf life stated on the product label is determined according to local climatic conditions. For advice, consult Hempel.
- Store the product in accordance with the Safety Data Sheet, label and local regulations. Keep containers in a dry, cool, well-ventilated place away from heat and sources of ignition. Keep containers tightly closed. Handle with care.
More information is available at the Knowledge Centre: https://www.hempel.com/knowledge-center. The following documents are in the “Technical Guidelines” section:
https://www.hempel.com/knowledge-center/technical-guidelines Hempel
| Number | Document description | Location/Notes |
| 3. | PDS | This document |
datasheet, which is also available for download at www.hempel.com.
This Product Data Sheet (“PDS”) relates to the product supplied (the “Product”), and its content is updated from time to time. Accordingly, the buyer/applicator should refer to the PDS supplied with the relevant batch of product (rather than an earlier version). In addition to the PDS, the buyer/applicator may receive some or all of the specifications, declarations and/or guides shown below, which are also available for download from the “Products” page of the Hempel website (www.hempel.com) (hereinafter the “Supplementary Documents”):
| 1. | Technical declaration | Provides one-off specific advice for the requirements of a specific project |
| 2. | Specifications | Issued for specific projects only |
| 4. | Explanatory notes to the PDS | Available for download at www.hempel.com, containing information related to product test parameters |
| 5. | Application guide | If available, provided at www.hempel.com |
| 6. | General technical guidelines (e.g. application and surface preparation) |
If the information in the PDS and the supplementary documents is inconsistent, the information shall take precedence in the order listed above. In this case, contact the Hempel representative for clarification. In addition, the buyer/applicator must give full consideration to the relevant safety information accompanying each product. Hempel accepts no liability for any defects arising from application not carried out fully in accordance with the recommendations and requirements of the relevant PDS and supplementary documents. The information and terms in this disclaimer apply to this PDS, the supplementary documents and any other relevant documents provided by Hempel for this product. In addition, unless otherwise expressly agreed in writing, supply of the product and all technical support are subject to Hempel's General Conditions of Sale, Delivery and Service.
Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.
Packaging specifications and batch lead times are subject to actual availability. PleaseContact Uscontact us for project-based calculation.