HEMPEL Fire Protection Coating 43600 is a fire protection coating. Used as an intumescent fire protection coating for structural steel under indoor and outdoor conditions, up to Type X (EAD350402-00-1106/EN 16623) and C4 category (ISO 12944-2). HEMPEL Fire Protection Coating 43600 is a one-component, solvent-borne, physically drying intumescent coating providing passive fire protection against cellulosic fires for steel structures over a range of time periods. Parameters on this page: volume solids 75 ± 3%, number of components: one-component. Comparable models from the same brand: HEMPEL Fire Protection Coating XTR 100, HEMPEL Waterborne Road Marking Paint 28100, HEMPEL Pure Acrylic Road Marking Paint 29680.
Parameter source: HEMPEL original technical data sheet (TDS) for HEMPEL Fire Protection Coating 43600; spreading rate and other values are converted from TDS parameters and provided for product selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.
This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.
| Volume Solids | 75 ± 3% |
|---|---|
| Dry Film Thickness | — |
| Theoretical Spreading Rate | — |
| VOC | 320 g/L (China) |
| Density / Specific Gravity | 1.3 kg/L |
| Number of Components | One-component |
| Flash Point | 23°C |
| Colour / Appearance | White 10000 |
| Gloss | Flat |
For more Q&A on selection, application, acceptance and defect diagnosis, seeFAQsection.
HEMPEL Fire Protection Coating 43600 is a one-component, solvent-borne, physically drying intumescent coating providing passive fire protection against cellulosic fires for steel structures over a range of time periods. Suitable for shop and site application, indoors and outdoors.
Used as an intumescent fire protection coating for structural steel under indoor and outdoor conditions, up to Type X (EAD350402-00-1106/EN 16623) and C4 category (ISO 12944-2). Suitable for I-beams, H columns, hollow sections and cellular beams.
Used for repair and touch-up of damaged areas after fresh application of HEMPEL Fire Protection Coating 43600.
- CE marked product under European Technical Assessment (ETA). ETA 12/0581. Up to 120 minutes.
- Reaction-to-fire tested in accordance with EN 13501-1 (using approved primers and topcoats, as part of a coating system).
- Approved and third-party certified in accordance with EN 13381-8, AS 4100 and GB 14907:2018. The product is CE marked under ETA and certified by ApplusFire.
- A dry film thickness of no more than 1500 µm [60 mil] per coat, so that only a few coats are required to provide the required protection.
- 12 months' weather resistance without a topcoat, provided the coating is fully dry, applied in accordance with the application instructions, and not exposed to condensation, running water or standing water.
- Third-party certified Environmental Product Declaration (Type III EPD, in accordance with ISO 14025 and EN 15804) is available. The product can contribute EPD credits for LEED and BREEAM projects.
- Complies with EU Directive 2004/42/EC, the Paints Directive on limiting volatile organic compounds: subcategory i.
| Product safety | Flash point 23 °C |
|---|
| Regulations | Value |
| European Union | 320 g/L |
| USA (coatings) | 320 g/L |
| USA (regulatory) | 320 g/L |
| China | 320 g/L |
| Hong Kong | 320 g/L |
| South Korea | 320 g/L |
In accordance with ISO 11890-1. ª EU Directive 2004/42/CE. Depending on specific legislation, see the explanatory notes provided on the Hempel website hempel.com or the local Hempel website. This product complies with the VOC requirements of national mandatory or national recommended standards; consult the company representative for details.
Handle with care. Before and during use, observe the safety labels on the packaging and paint containers and comply with all local and national safety regulations. Consult the Hempel Safety Data Sheet and Product Data Sheet for the product at all times.
For professional use only.
| Product code | 43600 |
|---|---|
| Standard colour / code | White 10000 |
| Gloss | Flat |
| Volume solids | 75 ± 3% |
| density | 1.3 kg/L |
- For approved substrates other than carbon steel, additional surface preparation steps may be required; refer to Hempel's application instructions for details.
For further details, refer to the separate Hempel document Surface Preparation Guide.
Thinner
| Cleaning solvent | HEMPEL's Thinner 08080 |
|---|
HEMPEL's Tool Cleaner 99610
| Tools | Application parameters |
|---|
Nozzle pressure: 20 MPa
Nozzle tip size: 0.43-0.58 mm. If brush or roller is used, multiple coats are required to achieve the specified dry film thickness. Thinning is generally not recommended. The spray parameters are indicative and may be adjusted according to site conditions. The pressure values apply to material at 20 °C. (*For other application methods, consult the company representative).
The dry film thickness of the fire protection coating depends on the required fire resistance rating and the section factor of the steel structure; contact your local Hempel representative. The maximum thickness per coat is 1500 µm [60 mil] dry film thickness, equivalent to 2000 µm [80 mil] wet film thickness. For further details, refer to the Application Instructions.
- Previous coat: according to Hempel's specification. Hempel-approved primers only. Consult the Hempel representative for information on approved primers.
- Subsequent coat: according to Hempel's specification. A range of approved topcoats is available. Consult the Hempel representative for information on approved topcoats.
- The topcoat cannot be applied until the specified intumescent thickness is reached and the coating is sufficiently dry. Consult the Hempel representative for further details.
- The Application Instructions detail the specific recommendations for selecting primers and topcoats for particular service environments.
| Ambient temperature | 25°C |
|---|---|
| Product | 15 months |
When stored in unopened original containers, shelf life is counted from the date of production. Thereafter, the product quality must be re-inspected. Storage at high temperatures may shorten the shelf life. For advice, consult Hempel.
- If the shelf life is exceeded, the product must be re-evaluated before use. Contact the Hempel representative.
- Store the product in accordance with the Safety Data Sheet, label and local regulations. Keep containers in a dry, cool, well-ventilated place away from heat and sources of ignition. Keep containers tightly closed. Handle with care.
For further information, refer to the Hempel website (https://www.hempel.com/service-and-support/technical-guidelines) or your local Hempel website:
| Number | Document description | Location/Notes |
| 3. | PDS | This document |
datasheet, which is also available for download at www.hempel.com.
This Product Data Sheet (“PDS”) relates to the product supplied (the “Product”), and its content is updated from time to time. Accordingly, the buyer/applicator should refer to the PDS supplied with the relevant batch of product (rather than an earlier version). In addition to the PDS, the buyer/applicator may receive some or all of the specifications, declarations and/or guides shown below, which are also available for download from the “Products” page of the Hempel website (www.hempel.com) (hereinafter the “Supplementary Documents”):
| 1. | Technical declaration | Provides one-off specific advice for the requirements of a specific project |
| 2. | Specifications | Issued for specific projects only |
| 4. | Explanatory notes to the PDS | Available for download at www.hempel.com, containing information related to product test parameters |
| 5. | Application guide | If available, provided at www.hempel.com |
| 6. | General technical guidelines (e.g. application and surface preparation) |
If the information in the PDS and the supplementary documents is inconsistent, the information shall take precedence in the order listed above. In this case, contact the Hempel representative for clarification. In addition, the buyer/applicator must give full consideration to the relevant safety information accompanying each product. Hempel accepts no liability for any defects arising from application not carried out fully in accordance with the recommendations and requirements of the relevant PDS and supplementary documents. The information and terms in this disclaimer apply to this PDS, the supplementary documents and any other relevant documents provided by Hempel for this product. In addition, unless otherwise expressly agreed in writing, supply of the product and all technical support are subject to Hempel's General Conditions of Sale, Delivery and Service.
Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.
Packaging specifications and batch lead times are subject to actual availability. PleaseContact Uscontact us for project-based calculation.