EPTANK362 Potable Water Tank Epoxy Tank Coating belongs to potable water tank coatings, epoxy system. Designed for application to tank interiors carrying potable water and fire-fighting water. Two-pack, white or pink, suitable for storage of potable water. Parameters on this page: dry film thickness 125 µm, theoretical spreading rate 3.8 m²/kg, number of components two-component.
Source of parameters: OSAKA original technical data sheet (TDS) "EPTANK362 Potable Water Tank Epoxy Tank Coating"; spreading rate and other values are converted from TDS parameters, for selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.
This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.
| Volume Solids | 63% |
|---|---|
| Dry Film Thickness | 125µm |
| Theoretical Spreading Rate | 3.8 m²/kg |
| VOC | 320 g/L |
| Density / Specific Gravity | Approx. 1.3 kg/L |
| Number of Components | Two-component |
| Flash Point | Above 23 °C |
| Thinner | OUP 103, recommended addition 3%–5% |
| Mixing Ratio | Component A : Component B = 5:1 (by weight) |
Two-pack, white or pink, suitable for storage of potable water.
Designed for application to tank interiors carrying potable water and fire-fighting water.
| Volume Solids | 63% |
|---|---|
| Dry Film Thickness | 125 µm equivalent to 200 µm wet film thickness. |
| Theoretical Spreading Rate | 3.8 m²/kg, based on dry film thickness of 125 µm. |
| Practical Spreading Rate | Allowing a suitable loss |
| Volatile organic compound content | 320 g/L |
| Mixing Ratio | Component A : Component B = 5:1 (by weight) |
|---|---|
| Airless spray | Recommended: tip size 0.53–0.69 mm; fluid pressure ≥ 19 MPa |
| Brush or roller | For small areas only, including touch-up; repeat application is required to achieve the specified film thickness. |
| Conventional spray | Suitable but not recommended. |
| Thinner | OUP 103, recommended addition 3%–5%. |
| Paint equipment cleaner | OUP 103 |
| Pot life | 23 °C: 6 h |
| Drying Time | ||||
| Substrate Temperature | Touch dry (h) | Hard dry (h) | Recoat Interval | |
| Minimum | Maximum | |||
| 5°C | 8 | 48 | 48 h | 28 days |
| 23°C | 1 | 24 | 24 h | 21 days |
| 35°C | 0.5 | 16 | 16 h | 14 days |
| Storage | Store in a cool, dry environment |
|---|---|
| Shelf life | 1 year |
| Packaging Specifications | Component A: 20 kg in a 20 L container; Component B: 4 kg in a 4 L container |
| Flash Point | Above 23 °C |
| density | Approx. 1.3 kg/L |
Consult the Company for detailed information on coating of tank interiors. Remove grease by solvent cleaning according to SSPC-SP1; where necessary, remove weld spatter, grind welds and sharp edges, and blast clean to white metal (SSPC-SP10 or Sa2.5 of ISO 8501:2007). Apply this paint before oxidation occurs; if oxidation has occurred, re-blast the oxidized areas to the specified standard. Ensure the surface is clean before application and apply the next coat of this paint within the specified recoat interval. Consult the Company for maintenance matters.
The Company shall be consulted to confirm that this tank coating is suitable for the cargo to be loaded. Drying time and recoat interval of this coating may vary with site factors such as tank shape and ventilation rate. The tank shall be thoroughly cleaned before loading potable water.
Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.
For more Q&A on selection, application, acceptance and defect diagnosis, seeFAQsection.
Packaging specifications and batch lead times are subject to actual availability. PleaseContact Uscontact us for project-based calculation.