← Back to JOTUN brand page
China-based coatings exporter — industrial & marine protective coatings from China's production bases

SteelMaster 120SB Intumescent Fire Protection Coating for Outdoor Steel Structures

Quick Specs

SteelMaster 120SB Exterior Intumescent Fire Protection Coating for Steel Structures belongs to fire protection coatings. With an approved topcoat, suitable for internal or semi-exposed steel structures up to C4 (ISO 12944-2). Independently certified for fire protection of structural steel exposed to cellulosic fires. Parameters on this page: volume solids 72 ± 3%, dry film thickness 200–720 µm, number of components single-component. Comparable models from the same brand: Jotachar 1709 XT epoxy intumescent coating, Jotachar 1709 exterior intumescent fire protection coating for steel structures, Jotachar JF750 XT epoxy intumescent coating.

Parameter source: JOTUN original Technical Data Sheet (TDS) 'SteelMaster 120SB Exterior Intumescent Fire Protection Coating for Steel Structures'; values such as spreading rate are converted from TDS parameters and are for selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.

This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.

Volume Solids72 ± 3%
Dry Film Thickness200–720 µm
Theoretical Spreading Rate—
VOC323 g/L
Density / Specific Gravity1.3 kg/L
Number of ComponentsOne-component
Flash Point25 °C
Wet Film Thickness280–1000 µm

Browse Similar Models by CategoryThis model belongs to: Fire Protection

FAQ

How many components does SteelMaster 120SB have?
SteelMaster 120SB is a single-component product; stir to uniformity after opening the can and apply. No on-site mixing is required.
What dry film thickness is typically applied for SteelMaster 120SB?
Typical dry film thickness of SteelMaster 120SB is 200–720 µm, determined by the coating system and design requirements.
What is the volume solids of SteelMaster 120SB?
Volume solids of SteelMaster 120SB: 72 ± 3%.
What is the VOC of SteelMaster 120SB?
VOC of SteelMaster 120SB: 323 g/L.
What is the flash point of SteelMaster 120SB?
Flash point of SteelMaster 120SB: 25°C. Storage, transport and application shall be in accordance with the product safety data sheet.
How long does SteelMaster 120SB take to dry?
Drying time of SteelMaster 120SB under standard conditions: touch dry 2 h; actual drying is affected by temperature, film thickness and ventilation.
Which standards apply to SteelMaster 120SB?
As recorded in the technical data on this page: suitable for interior or semi-exposed locations of steel structures up to C4 (ISO 12944-2); GB14907:2018 (see the application instructions on this page). Specific applicability is subject to the manufacturer's technical data sheet and the coating system.
Where can SteelMaster 120SB be purchased?
RichTech Industrial Technology (Shanghai) Co., Ltd. distributes industrial and marine coatings, representing brands including JOTUN, HEMPEL, International, PPG and KANSAI, and provides product selection, coating systems and quantity calculations. Company address: Changhui Building, 799 Yinxiang Road, Jiading District, Shanghai.

Exterior Intumescent Fire Protection for Structural Steel (0S6)

Product description

This is a single-component solvent-borne thin-film intumescent acrylic coating. Independently certified for fire protection of structural steel exposed to cellulosic fires. Suitable as an intermediate or topcoat in atmospheric environments. Suitable for carbon steel substrates with an approved primer.

Typical Use

Specially designed as a reactive fire protection system for steel structures. With an approved topcoat, suitable for internal or semi-exposed steel structures up to C4 (ISO 12944-2).

SteelMaster 120SB adequately dried during the construction phase may be exposed for 6 months without a topcoat; regardless of whether a topcoat is applied, the fire protection coating shall be protected from condensation, standing or ponding water from rain or water spray, snow and freezing.

Contact your local JOTUN representative for the detailed application procedure document.

Others

Approvals and Certificates

BS 476 Part 20/21: Certifire CF 845 applicable to open web beams (RT1356)

Chinese GB14907:2018 ASTM E84: Class A. Other certificates and approvals are available on request.

Colour

White

Product Data

PropertyTest / StandardDescription
Volume SolidsISO 323372± 3 %
Flash PointISO 3679 Method 125 °C
DensityTheoretical Value1.3 kg/L
VOC — USA / Hong KongUS EPA Method 24 (test value) (CARB (SCM) 2007, SCAQMD Rule 1113, Hong Kong)323 g/L
VOC — EUIED (2010/75/EU) (theoretical value)351 g/L
VOC — ChinaGB/T 23985-2009 (tested)355 g/L

The data listed are based on factory batch production and may vary slightly with colour.

Solids content measured according to ISO 3233 and the ASFP-BCF guidance method

Film Thickness per Coat

Typical recommended specification range

Dry Film Thickness200–720 µm
Wet Film Thickness280–1000 µm

All steelwork must be coated at the correct film thickness to achieve the required fire rating. Refer to the current thickness tables. For details, consult your local JOTUN office.

NoteThe single-coat film thickness applies to airless spray only.

Surface Preparation

For further information, see the Application Guide.

Surface Preparation Summary

Surface Preparation

SubstrateMinimumRecommended
Coated surfaceA clean, dry and sound compatible primer.

Application

Application Methods

This product may be applied by the following methods

Spray:Apply by airless spray.
Brush:Recommended for touch-up and small-area application. Take care to achieve the specified dry film thickness.

Product mixing

One-component

Thinner / Cleaning Solvent

Do not add thinner. Not to be thinned; ready for use.

CleanerJOTUN Thinner No. 7

When the thinner is used as a cleaning solvent, it must first comply with local regulatory requirements

Airless Spray Guidance

Nozzle tip size (inch/1000):19-23
Nozzle pressure (minimum):200 bar/2900 psi

Drying and Curing Time

Substrate Temperature5 °C10 °C23 °C40 °C
Touch Dry2 h1 h30 min20 min
Handle dry48 h24 h16 h8 h
Minimum recoat interval24 h8 h6 h

For the maximum recoat interval, refer to the Application Guide (AG) for this product.

The minimum drying recoat interval is for self-recoating. See the additional guidance for the finish coat.

All drying times are measured at a wet film thickness of 1000 µm, under controlled temperature and at a relative humidity below 85%.

Drying time may vary with changing ambient conditions, such as air temperature, relative humidity, climatic conditions, ventilation, number of coats and total dry film thickness applied. Refer to the application guide for application of multiple coats.

Topcoat

With an approved acrylic topcoat, the recommended minimum recoat interval for this product is 24 h; with other approved topcoats, 48 h. The system shall be dry to handle, and the dry film thickness gauge shall not leave marks on the coating surface. Where temperature falls or a multi-coat system is applied, drying time and recoat interval may be extended. Before applying the topcoat, applicators shall confirm the specified dry film thickness has been achieved.

Touch DryThe state at which light finger pressure leaves no mark or stickiness.
Handle dryThe minimum time after application before handling will not damage the film.

Minimum recoat interval after drying: the recommended minimum interval before applying the next coat.

Product Compatibility

Depending on the actual exposure conditions in service, this product may be used with various primers and topcoats. Some reference systems are listed below. For specific systems, contact JOTUN.

Previous coat:Alkyd, epoxy, epoxy zinc phosphate, zinc epoxy (with epoxy tie coat)
Subsequent coat:Approved topcoat list

The compatible primer and topcoat shall be compatible with the fire protection coating to ensure its fire performance:

SteelMaster 120SB Exterior Intumescent Fire Protection Coating for Steel Structures (0S6)

Contact your local JOTUN office for the approved primer and topcoat list.

Typical Packaging Sizes

VolumeContainer Size
(L)
Exterior Intumescent Fire Protection for Structural Steel (0S6)20

The packaging sizes above are typical reference sizes for factory batch production. Due to regional regulatory differences, packaging sizes and capacities may vary by region.

Storage

Store in accordance with national regulations. Keep in a dry, cool, well-ventilated place away from heat and sources of ignition. Keep containers tightly closed. Handle with care.

Shelf Life at 23 °C

Exterior Intumescent Fire Protection Coating for Steel Structures (0S6) 18 months

In some markets, the stated shelf life may be shortened to comply with local legal requirements. The above is the minimum shelf life; thereafter, testing is required to confirm quality remains acceptable.

Precautions

For professional use only. Applicators and workers must be trained, experienced, capable and equipped to mix, stir and apply the coating correctly in accordance with JOTUN's technical documents. Applicators and workers must wear appropriate personal protective equipment when using this product. This guidance is provided based on current product knowledge. Any proposed modification to suit site conditions must be approved by the responsible JOTUN representative before use.

Health and Safety

Read the safety warnings on the container packaging. Use in well-ventilated conditions. Avoid inhaling spray mist and avoid skin contact. In case of accidental splashes on skin, wash immediately with a suitable cleaner, soap and water. In case of eye contact, rinse thoroughly with water and seek medical attention immediately.

Colour Variation

When used primarily as a primer or antifouling coating, products may show slight colour variation from batch to batch. Such products, and epoxy products used as topcoats, may chalk when exposed to sunlight.

Gloss and colour retention of topcoats depend on the colour type, the surrounding environment such as temperature and UV intensity, application quality and product type. Contact your local JOTUN office for further information.

Disclaimer

The information in this datasheet is based entirely on knowledge gained in our laboratory and in practice. JOTUN products are regarded as semi-finished products, and their use is generally beyond our control. JOTUN therefore guarantees only the quality of the product itself. To comply with local regulations, the product may be adjusted, and we reserve the right to modify the datasheet without further notice.

Users should consult JOTUN for specific guidance on the suitability of the product for their requirements and applications.

In case of any discrepancy between language versions, the English (UK) version shall prevail.

Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.

Similar models from the same brand — Fire protection

View all JOTUN models

Purchase & Documents

Packaging specifications and batch lead times are subject to actual availability. PleaseContact Uscontact us for project-based calculation.

China production baseIndustrial & marine coatingsWorldwide delivery