Jotatherm TB550 Low-temperature Spill Protection Coating TB550 belongs to thermal insulation coatings, epoxy coating system. Fire protection: can be used in combination with Jotachar epoxy passive fire protection coating to reduce substrate surface temperature to below 80°C, protecting Jotachar against heat radiation from the substrate. The product can be used alone or together with Jotachar epoxy passive fire protection coating. Parameters on this page: volume solids 100%, number of components two-component. Similar products from the same brand for comparison: Balloxy BT Modified Epoxy Primer BT, Jota Armour II Three-component Abrasion-resistant Polyamine-cured Epoxy Coating, Jota EP15 MIO Fast-drying Epoxy MIO Intermediate Coat.
Parameter source: JOTUN original Technical Data Sheet (TDS) 'Jotatherm TB550 Low-temperature Spill Protection Coating TB550'; values such as spreading rate are converted from TDS parameters and are for product selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.
This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.
| Volume Solids | 100% |
|---|---|
| Dry Film Thickness | — |
| Theoretical Spreading Rate | — |
| VOC | 0 g/L |
| Density / Specific Gravity | Specific gravity: 0.57 g/cm³. |
| Number of Components | Two-component |
| Flash Point | 100 °C |
| Mixing Ratio | 2.4 parts : 1 part (by weight) |
| Shelf life | 12 months : 12 months |
For more Q&A on selection, application, acceptance and defect diagnosis, seeFAQsection.
Low-temperature Spill Protection Coating TB550 (0L9)
Two-component solvent-free amine-cured synthetic epoxy insulating coating. Provides thermal insulation and anti-corrosion protection. Suitable for continuous operating temperatures from -40°C to 150°C. Can be used alone or together with Jotachar epoxy passive fire protection coating.
Typically used in the oil, gas and energy industries. Suitable for offshore and coastal environments.
Resistance to cryogenic liquid spillage:
When applying Jotatherm TB550, it acts only as part of the system to resist embrittlement of the substrate caused by spillage of cryogenic liquids such as LNG.
The Jotatherm CSP1 mesh shall be applied as described in the Jotatherm TB550 application guide to resist cryogenic liquid spillage.
Fire protection:
Can be used in combination with Jotachar epoxy passive fire protection coating to reduce substrate surface temperature to below 80°C, protecting Jotachar against heat radiation from the substrate.
Thermal insulation:
Can be used to reduce substrate temperature to provide personnel protection. Provides thermal insulation and corrosion protection under insulation. Suitable for continuous operating temperatures from -40°C to 150°C.
Others
ISO 20088-1 low-temperature spill resistance; NORSOK M-501, Rev. 6; ISO 20340 cyclic durability test; ASTM C177 – thermal conductivity; ASTM E228 – thermal expansion; ASTM E1269 – specific heat capacity. In combination with Jotachar, the following fire tests are passed:
- ISO 834-3/BS476 hydrocarbon pool fire test - ISO 22899 jet fire resistance test for passive fire protection materials. Other certificates and approvals are available upon request.
Light yellow
| Property | Test / Standard | Description |
| Volume Solids | ISO 3233 | 100% |
| Flash Point | ISO 3679 Method 1 | 100 °C |
| VOC — USA / Hong Kong | US EPA Method 24 (test value) (CARB (SCM) 2007, SCAQMD Rule 1113, Hong Kong) | 0 g/L |
The data listed are based on factory batch production and may vary slightly with colour.
Application specific gravity (ISO 1183:1987 Method A): 0.57 g/cm³.
Typical recommended specification range:
Dry film thickness:
2–40 mm (depending on application purpose and specific project requirements)
Spray application:
| Typical maximum film thickness achievable per coat | 5 mm |
|---|
Manual application:
| Typical maximum film thickness achievable per coat | 25+ mm |
|---|
Film thickness depends on the shape and structure of the steel structure, surrounding environment, pump type and settings, primer used and other factors.
Absolute maximum DFT is the highest DFT achievable after application without sagging.
To ensure lasting adhesion of the next coat, all surfaces must be clean, dry and free of contaminants.
Surface Preparation
| Substrate | Minimum | Recommended |
| Coated surface | A clean, dry and sound compatible primer. | |
This product may be applied by the following methods
| Spray: | Use a heatable two-component plural-component pump. For more information, refer to the application guide. Note: all spray pumps used for this product must be certified by JOTUN. |
| Trowel: | For further information, see the Application Guide. |
| Mesh installation | When Jotatherm TB550 is used for low-temperature protection, Jotatherm CSP1 mesh shall be installed. For more information, refer to the application guide. |
|---|
| Cryogenic Spill Protection Coating TB550, Component A | 2.4 parts |
| Cryogenic Spill Protection Coating TB550, Component B | 1 part |
Each component must be stored at 25–30 °C (77–86 °F) for 24 hours. Stir or mix thoroughly with a power mixer before application.
Do not add thinner.
| Cleaner | JOTUN Thinner No. 7 / JOTUN Thinner No. 10. For roller application, use JOTUN Thinner No. 7 and No. 17. |
|---|
When the thinner is used as a cleaning solvent, it must first comply with local regulatory requirements
In China, the cleaning solvent must comply with GB 38505-2020
| Nozzle tip size (inch/1000): | 27-35 |
| Nozzle pressure (minimum): | 200 bar/2900 psi |
| Substrate Temperature | 5 °C | 15 °C | 23 °C | 40 °C |
| Touch Dry | 6 h | 3 h | 1 h | |
| Walk-on Dry | 36 h | 12 h | 6 h | 3 h |
| Minimum recoat interval | 6 h | 3 h | 1 h | |
| Dry/cured to service | 36 h | 12 h | 6 h | 3 h |
For the maximum recoat interval, refer to the Application Guide (AG) for this product.
Drying and curing times are determined based on temperature and relative humidity below 85%, with dry film thickness within the average range.
| Touch Dry | The state at which light finger pressure leaves no mark or stickiness. |
|---|---|
| Walk-on Dry | The minimum time after which the coating allows normal foot traffic without leaving permanent footprints, marks or other physical damage. |
Minimum recoat interval after drying: the recommended minimum interval before applying the next coat.
Dry/cured to service: the minimum time before the coating can be permanently exposed to a specific environment/medium.
| Paint temperature | 15 °C | 23 °C |
| Pot Life | 40 min | 25 min |
The given parameters apply to trowel application and roller application.
The working pot life does not apply to two-component spray equipment, as the materials are mixed within the spray gun during application. For manual application, mixed material shall be used as soon as possible. As the reaction is exothermic, the larger the mixed quantity, the shorter the pot life.
Temperature
| Continuous | Peak | |
| Drying, atmospheric | 150°C | - |
Depending on the actual exposure conditions in service, this product may be used with various primers and topcoats. Some reference systems are listed below. For specific systems, contact JOTUN.
| Previous coat: | Epoxy, zinc epoxy, epoxy zinc phosphate, modified epoxy |
| Subsequent coat: | Polyurethane, polysiloxane, epoxy, epoxy passive fire protection |
Primers used beneath this product must be approved by JOTUN. Consult JOTUN for the latest approved primer list.
Refer to the application manual.
| Cryogenic Spill Protection Coating TB550, Component A | Weight 8.8 kg | Container size (L) 20 |
| Cryogenic Spill Protection Coating TB550, Component B | 7.3 kg | 20 |
One Jotatherm TB550 kit consists of two drums of 8.8 kg Component A and one drum of 7.3 kg Component B.
The packaging sizes above are typical reference sizes for factory batch production. Due to regional regulatory differences, packaging sizes and capacities may vary by region.
Store in accordance with national regulations. Keep in a dry, cool, well-ventilated place away from heat and sources of ignition. Keep containers tightly closed. Handle with care.
• Normal storage temperature: minimum 1°C (34°F), maximum 35°C (95°F).
• For two-component spray equipment, preheat at 40–50°C (113–122°F) for at least 12 h before use.
• For manual application at ambient temperature below 20°C (68°F), preheat the paint at 20–35°C (68–95°F) for at least 12 h before use.
Protect from frost.
| Cryogenic Spill Protection Coating TB550, Component A | 12 months |
| Cryogenic Spill Protection Coating TB550, Component B | 12 months |
In some markets, the stated shelf life may be shortened to comply with local legal requirements. The above is the minimum shelf life; thereafter, testing is required to confirm quality remains acceptable.
For professional use only. Applicators and workers must be trained, experienced, capable and equipped to mix, stir and apply the coating correctly in accordance with JOTUN's technical documents. Applicators and workers must wear appropriate personal protective equipment when using this product. This guidance is provided based on current product knowledge. Any proposed modification to suit site conditions must be approved by the responsible JOTUN representative before use.
Read the safety warnings on the container packaging. Use in well-ventilated conditions. Avoid inhaling spray mist and avoid skin contact. In case of accidental splashes on skin, wash immediately with a suitable cleaner, soap and water. In case of eye contact, rinse thoroughly with water and seek medical attention immediately.
When used primarily as a primer or antifouling coating, products may show slight colour variation from batch to batch. Such products, and epoxy products used as topcoats, may chalk when exposed to sunlight.
Gloss and colour retention of topcoats depend on the colour type, the surrounding environment such as temperature and UV intensity, application quality and product type. Contact your local JOTUN office for further information.
The information in this datasheet is based entirely on knowledge gained in our laboratory and in practice. JOTUN products are regarded as semi-finished products, and their use is generally beyond our control. JOTUN therefore guarantees only the quality of the product itself. To comply with local regulations, the product may be adjusted, and we reserve the right to modify the datasheet without further notice.
Users should consult JOTUN for specific guidance on the suitability of the product for their requirements and applications.
In case of any discrepancy between language versions, the English (UK) version shall prevail.
Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.
Packaging specifications and batch lead times are subject to actual availability. PleaseContact Uscontact us for project-based calculation.